14.3 Screen: Security Passwords & Key-
pad
The UPS has several levels of security password avail-
able: USER
(USR) , ADMIN (ADM), and other security
levels for use by service and factory representatives.
The security level is indicated on the Security Key.
The UPS stays in a security level until a new level is
entered.
For example, once the UPS is placed in the USR level, it
remains at that level until the security level is changed.
Login:
1.
Press the Security Level key,
2.
The keypad replaces the Main screen to allow en-
tering the password. By default the password are
set to:
User: USER
Administrator: ADMIN
3.
Typing in USER in the keypad will change the se-
curity level to User. Enter the password using the
alphanumeric keys.
4.
Press Write to store the password in the UPS. If
the password is accepted the text "Successful" will
display at the bottom left of the touchpad, as shown
here.
If the password entered was not accepted, the text
"Error15 – Write Function" or some similar message will
indicate that the password or level change was not ac-
cepted.
5.
Press the QUIT key and the keypad will close and
the original display restored.
This same keypad is used for data input for
parameters in the Settings tab.
28
96%
HOME
Main
619 Change Secu. Lvl
USER
1./
.
USR
4GHI
7PQRS
Successful
DVCOH
1600XP Series Installation and Operation Manual
100%
INV
12:35 PM
USR
Monitor
Settings
2ABC
3DEF
5JKL
6MNO
8TUV
9WXYZ
0-:
Shift
ASYN
KEYPAD
Records
Quit
Write