3. Important Safety Instructions

This manual contains important instructions that should be followed during the installation and maintenance
of the UPS and its batteries.
Hardwired UPS units are not equipped with an over-current protection device nor an output disconnect for
the AC output. A circuit breaker should be provided by the user between the UPS output and the load input.
This device should be rated as follows:
3.6 kVA
240VAC
RATING
20 A
* Ratings are for an 80% rated device.
The nominal battery voltages for these models are as follows:
3.6 kVA
BATTERY
VOLTAGE
144 Vdc
Servicing of the batteries should only be performed by a qualified factory authorized representative who
is knowledgeable about batteries and the required precautions. Keep unauthorized personnel away from
batteries. To arrange for battery replacement, contact Toshiba Customer Support Center.
1.
Turn off, lockout, and tagout all equipment before connecting the power wiring to the equipment or
when performing maintenance.
2.
The maximum ambient operating temperature is 104 °F (40 °C).
3.
Access panels should only be removed by authorized Toshiba field Service personnel.
4.
UPS servicing should be performed by qualified Toshiba representatives only.
5.
Battery servicing should be performed by qualified Toshiba representatives only.
6.
Contact your Toshiba authorized service center for battery replacement.
1600XP Series Installation and Operation Manual
6 kVA
8 kVA
10 kVA
35 A
45 A
60 A
6 kVA
8 kVA
10 kVA
216 Vdc
288 Vdc
288 Vdc
14 kVA
18 kVA
22 kVA
80 A
100 A
125 A
14 kVA
18 kVA
22 kVA
288 Vdc
288 Vdc
288 Vdc
5