19. Optional MB (Maintenance Bypass) Units

The following illustration shows the circuit power flow when the UPS is operating in the optional Mainte-
nance Bypass mode. The input jumper on the UPS must be set for 240 VAC.
Ensure the UPS is in Static Bypass before switching the unit from UPS to Maintenance
Bypass mode or from Maintenance Bypass to UPS mode. Failure to do so could result
in damage to the maintenance bypass switch or the UPS.
This Maintenance Bypass unit can only be used for 240 V applications. Ensure the
UPS voltage selector jumper is set to 240 V. See page 12 for the correct 240 V setting.
MCCB
Input
Line Filter
Power
Surge
Absorber
POWER FLOW IN MAINTENANCE BYPASS MODE FOR ALL MODELS

19.1 Internal Maintenance Bypass

The optional internal maintenance bypass is mounted on the rear of the UPS.
Internal Maintenance Bypass Instructions:
From Inverter Mode to Maintenance Bypass Mode
1.
Turn the RUN/STOP switch to the STOP position on the UPS.
2.
Turn the Maintenance Bypass Switch to the Bypass position. The Bypass LED should be ON and the
UPS LED should be OFF. The LEDs are next to the Maintenance Bypass switch, on the back of the
UPS.
3.
Turn the MCCB input breaker on the UPS to the OFF position. The UPS is now operating in Mainte-
nance Bypass Mode.
From Maintenance Bypass Mode to Inverter Mode
1.
Turn the MCCB input breaker on the UPS to the ON position.
2.
Turn the Maintenance Bypass switch to the UPS position. The UPS LED should be ON and the Bypass
LED OFF.
3.
Turn the RUN/STOP switch to the RUN position on the UPS. The UPS is now operating in the UPS
Mode.
42
NOTICE
Bypass
*Static Switch
Input
Fuse
Rectifier/
Inverter
Chopper
+
Batteries
* Switches are
solid state
devices.
Negative
Bus
1600XP Series Installation and Operation Manual
Maintenance
Bypass Switch
Isolation
Transformer
Output
Fuse
Power Flow
Output
Power