13.3 Status Indicators
The four top and three bottom UPS status Indicators on the main screen and their meanings are listed in
the table below.
Indicator
96%
Shows the current load percentage.
Battery Information: In On-line and Battery Back-up mode the display alternates between
battery charge percentage and estimated remaining battery runtime in:
100% / 11'
Minutes for Runtimes > 10 min.
100% / 9' 35"
Minutes and Seconds for Runtimes < 10 min.
100% / N/A
In other modes, the display alternates between battery charge percentage and "N/A."
Shows current UPS Status. Indicator will change as the UPS status changes. For a
INV
detailed listing see page 50.
12:35 PM
System Time
DVCOH
Fault Description Code - For a detailed listing see 47.
ASYN
Warning Description Code - For a detailed listing see page 48.
On-Line
Current operating mode of the UPS - For a detailed listing see page 50.
13.4 Light Emitting Diodes (LED)
The following table describes the front panel LED behaviors and the associated meaning.
LED
Behavior
Green - ON
Green - OFF
Green - OFF
On-Line/
Red - ON
Fault
Red - Flashing
Red - OFF
Amber - ON
Amber - Flashing
Warning
Amber - OFF
Green - ON
Green - Flashing
AC Input
Green - OFF
NOTE: On-Line/Fault LEDs - Appear Amber if Green and Red flash concurrently.
1600XP Series Installation and Operation Manual
Functional Description
Significance/Meaning
UPS is in On-Line, Backup, or Battery Test mode.
UPS in Bypass mode.
Load Discharging
One or more faults occurred. See Records: Faults for details.
Charger overvoltage occurred.
No fault occurred.
Service Call needed, Less than 6 mo. of Battery Life or Battery Life
End.
One or more Warnings occurred. See Records: Warnings for details.
No Warning (Normal, UPS in operation).
Input voltage is within specified range.
Input voltage is over specified range.
Input voltage is under specified range.
25