Toshiba 1600XP SERIES Installation And Operation Manual page 71

1600xp series single phase - 3.6/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

Capacity
Environment
Operating Temperature
59 – 77 °F (15 – 25 °C)
Recommended
Storage Temperature
Installation Area
Operating Humidity
Altitude
Acoustical Noise
Heat Generation (Typical)
Operation Diagnosis
Battery Check
Input OV Protection
Battery Lifetime
Internal Temperature
Event Data Storage
Applications
Switches
Bypass Switch
Bypass Disable
Automatic Retransfer
Interface/Communications
Real Time clock
Schedule Operation
Autostart
Remote ON/OFF
LED Display
Operator Interface
Buzzer Volume
Power Connections
Emergency Power Off
Remote Contacts
RS232 ASCII Interface
1.
Input/output figures rated for 240 volts unless otherwise stated.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%
3.
Subject to update without notice.
4.
Derate to 18.7 kVA (15.9 kW) for 50 Hz operation.
1600XP Series Installation and Operation Manual
STANDARD MODELS: 14 – 22 KVA (CONT'D)
14 kVA (11.9 kW)
1
60 Hz 32 – 104 °F (0 – 40 °C)
50 Hz 32 – 91 °F (0 – 33 °C)
-4 – 104 °F (-20 – 40 °C)
To be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
30 – 90% (no condensation)
< 6600 ft. (2000 m) above sea level
50 dB (A) maximum @ 1 meter from front panel
6610 BTU/Hr
3
Performed on start up, by schedule, on-demand (user configurable)
UPS calculates battery replacement time based upon
battery ambient temperature (LCD display, LED and beeps)
UPS gives indication of internal temperature, alarm when high temp
32 – Operation, 32 – Backup, 32 - Warnings, 32 – Faults, 32 - Test,
Static switch <1/4 cycle (50Hz: 5 ms/60Hz: 4.16 ms)
Factory or authorized service center selectable only
Real Time Clock with backup Lithium Ion Battery
Schedule ON/OFF operation of UPS using optional RemotEye III communication
Automatic UPS Startup when AC is applied - Option can be enabled or disabled at
Standard – External terminal
3 LED's indicating On-Line/Fault, Warning, and A/C Input
Standard (Fixed Volume)
Standard – Terminal contacts only
Standard (INV, BYP, BATT, LB, AC, FLT)
Toshiba UPS Communication Protocol 2.0
18 kVA (15.3 kW)
22 kVA (18.7 kW)
1
8499 BTU/Hr
3
Standard
32 - System
Generator compatible
software
user's discretion
Interactive Touchscreen
Standard – Hard wire
Output ratings given for 0.85PF are only valid
1, 4
2
10,387 BTU/Hr
3
A5

Hide quick links:

Advertisement

Table of Contents