Return Temperature Limit For Hot-Water Loading - Honeywell SDC heating and district heating controller Service Manual

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
7.2.4
EN2H-0221GE51 R0808
Besides return temperature limitation either volume flow limit or
thermal output limit can also be set for this controller. The
selection of these functions is described below in parameter 11.
Para-
Designation
meter
08
Max. return
setpoint
09
Starting point
of the flexible
district heating
return
temperature
11
Return limit
0 =
Temperature
1 = Volume
flow and
temperature
2 = Heat output
and
temperature

Return temperature limit for hot-water loading

In the case of hot-water loading a special constant return setpoint
applies. It is valid only if the hot-water loading pump is operating.
The return setpoint is to be set with parameter 10.
Para-
Designation
meter
10
Hot-water
circuit loading:
Target return
Range
Pre-
setting
0 ... 100
90
Off
Off
–40...+10
0 / 1 / 2
0
Range
Presetti
ng
40 ... 100
90
Hydraulic Components
Step
Unit
0.5
°C
0.5
°C
-
-
Step
Unit
°C
0.5
149