Night-Time Room Temperature" Button; Daytime Hot-Water Temperature" Button - Honeywell SDC heating and district heating controller Service Manual

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
5.1.2.3
¦
Setting
Factory setting
Setting range
5.1.2.4
§
Setting
Factory setting
EN2H-0221GE51 R0808

"Night-time room temperature" button

Sets the lowered room temperature in automatic mode between
the heating cycles and in the ABSENT and RED. HEATING
operating modes.
In operating mode 1, the set value for all heating circuits is the
same. In operating mode 2, the set value applies for the
respective heating circuit. To set the operating mode, see
5.2.3.3 Operating mode, pg. 74.
► Press
¦
button.
► Set flashing room temperature specification to the desired
value by turning the input button
C
► Confirm set value by pressing the
î
button
.
Alternative: Automatic acceptance of the value after the set
information time (see 5.1.2.7 "System information" button, pg. 35).
16 °C
5 ... 30 °C

"Daytime hot-water temperature" button

Sets the daytime hot-water temperature during the hot-water
operational-readiness times in automatic mode and in the PARTY
and HEATING operating modes. This set value also applies for
exclusively hot-water operation (manual summer operation).
§
► Press
button.
► Set flashing hot-water temperature to the desired value by
turning the input button
C
► Confirm set value by pressing the
button
î
.
Alternative: Automatic acceptance of the value after the set
information time (see 5.1.2.7 "System information" button, pg. 35).
50 °C
î
.
¦
button or the input
î
.
§
button or the input
Operation