Honeywell SDC heating and district heating controller Service Manual page 97

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
Para-
Designation
meter
11
Constant tem-
perature setpoint
(only if output was
set to constant
regulator)
12
Minimum
temperature limit
13
Maximum
temperature limit
14
Temperature
increase of heating
circuit
15
Follow-up time of
pump
16
Screed function
17
Return maximum
temperature limit
18*
P part X
P
19*
Sampling time T
20*
I part T
n
21*
Actuator runtime
22*
Actuator end
position function
23
Room control C-
factor (SDW 30
only)
EN2H-0221GE51 R0808
Setting range / Setting values
10 ... 95°C
10°C to setting value of
parameter 13
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
–5 ... 20 K
0 ... 60 min
OFF
1
Functional heating
2
Screed-drying heating
10 ... 90 °C
1 ... 50 %/K
1 ... 600 s
s
1 ... 600 s
10 ... 600 s
1
Continuous control
signal in end position
2
Control signal
suppressed at end
position (actuator de-
energised)
1 ... 100
Operation
Factory
Setting
setting
20
20
75
Mixed
heating
circuit = 4
5
OFF
90
2
20
270
120
1
8
97