Operation
Para-
Designation
meter
07
Hot-water circuit
operating mode
08
Tank discharge
protection
09
Temperature in-
crease of heat
generator with hot-
water circuit
charging
10
Switching
differential of hot-
water circuit
11
Hot-water charging
pump follow-up
time
90
Setting range / Setting values
1
Parallel operation
2
Priority operation
3
Conditional priority
4
Parallel operation based
on weather conditions
5
Priority operation with
intermediate heating
6
Priority isolating circuit
7
External operation
8
Conditional parallel
operation for mixed
heating circuit (DHC
only)
OFF
No discharge protection
ON
Discharge protection
activated
0 ... 50 K
Difference between hot-water
circuit charging temperature and
hot-water circuit setpoint
temperature
2 ... 20 K
Value of hot-water circuit switch-
ing differential. Symmetrical
effect around the hot-water circuit
setpoint
0 ... 60 min
SDC / DHC
Factory
Setting
setting
2
ON
15
5
5
EN2H-0221GE51 R0808
Need help?