Para-
Designation
meter
10
Reset heat
balance
11
Volume flow
12
Density of medium
13
Heat capacity of
medium
14
Final switch-off
temperature
15
Test cycle of solar
charging
switchover
16
Switchover tem-
perature
5.4.10
Para-
Designation
meter
01
Minimum
temperature
02
Maximum
temperature
03
Switch-on
differential
04
Switch-off
differential
05
Heat generator
cycle inhibitor
EN2H-0221GE51 R0808
Setting range / Setting values
SET by pressing the input button
0 ... 30 L/min or L/pulse
0.8 ... 1.2 kg/L
2 ... 5 KJ/kgK
OFF, 90 to 210 °C
1 ... 60 min
20 ... 110 °C

"Solid" menu (SOLID FUEL)

The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Setting range / Setting values
20 ... 80 °C
30 ... 100 °C
(Setting value of parameter
04 + 3 K) to 20 K
2 K to (setting value of parameter
03 – 3 K)
OFF, 2 to 180 min
Operation
Factory
Setting
setting
0
1.05
3.6
210
10
75
Factory
Setting
setting
60
90
10
5
OFF
107