Operation
Para-
Designation
meter
24
Room control T
(SDW 30 only)
25
Holiday operating
mode
26
Room setpoint
ramp
28
Cooling
temperature of
mixed heating
circuit
39
Spread of hot-
water circuit pre-
regulator
40
Offset valve
position of hot-
water circuit pre-
regulator
41
Switch-on op-
timisation
42
Minimum pre-heat
time
43
Maximum pre-heat
time
44
Min. jump back
temperature
45
Without room
sensor
46
Pre-heat time at
0 °C
47
Lowering ramp
98
Setting range / Setting values
5 ... 240 min
n
STBY
Standby
RED
Lowering operation
OFF, 0.5 ... 60 K/h
OFF, 18 to 24
2 ... 20 K
0 ... 100 %
OFF
1
Adaptation off
2
Adaptation on
3
Adaptation restart
0 ... setting value of parameter 43 0.5
Setting value of parameter 42 to
30 h
0 ... 30 °C
0 ... 10 °C
0 ... 30 h
0 ... 500 %
SDC / DHC
Factory
Setting
setting
35
STBY
OFF
OFF
5
0
OFF
5
5
1
1
100
EN2H-0221GE51 R0808