Honeywell SDC heating and district heating controller Service Manual page 133

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
EN2H-0221GE51 R0808
Combined operation for 2-stage heat generators
As long as just one stage can meet the heat demand (stage II
inactive), stage I is switched according to switching
differential I.
As soon as stage 2 is needed to meet the heat demand,
switching differential I takes over the switching on and off of
stage II and switching differential II takes over the switching of
stage I.
a
x
b
s
1)
c
d
i
f
g
a
Switch-off level stage I
b
Switch-off level stage II
c
Switch-on level stage II
d
Switch-on level stage I
e
Swap of switching
differential
f
Theoretical progression
with stage I alone
1) Temperature drop becomes slower after every switch-off of
stage II, as stage I provides support.
2) Switch-on level stage II is no longer reached, temperature is
reached from stage I.
3) Temperature drops due to increased heat demand under
switch-on level stage II.
e
b
a
2 )
d
i
c
h
g Area 1 high use (start-up),
coverage of heating demand at
full load (burner stages I and II)
h Area 2 low use, coverage of
heat demand with partial load
(burner stage I only)
i
Area 3 increased use,
coverage of heating demand at
full load (both burner stages)
x Boiler temperature
y Time
Hydraulic Components
e
a
b
3 )
c
d
i
i
y