Hydraulic Components
146
temperature according to the required setpoint within its limits.
The "Proportional Range", "Adjustment Time" and "Motor
Runtime" control parameters can be set in parameters 04 and 05.
Para-
Designation
meter
04
S gain
05
Adjustment
time
0 = pure
P controller
06
Runtime of
district
heating valve
Range
Presetti
ng
0,1 ... 30
5
0 ... 60
3
10 ... 1800 120
SDC / DHC
Step
Unit
0.1
%/K
1
min
1
s
EN2H-0221GE51 R0808