8.9. Parameter data

It is explanation by the reference method of the list of parameters of the VF-MB1 or
VF-S15 series as follows. For communication purpose, see the parameter list on
inverter's instruction manual regarding the communication number, adjustment range and
so forth.
<Example of excerpts from the inverter's instruction manual>
Communi-
Title
Function
cation No.
au
-
History function
h
0093
Guidance function
au
f
0094
Overload
au
l
characteristic
selection
de
0010
Deceleration time 1
c
ty
0007
Factory default setting
p
*1: Default values vary depending on the capacity.
*2: Changing the parameter
(1)
"Title" means the display on the inverter panel.
(2)
"Communication number" is affixed to each parameter that is necessary for designating the
parameter for communication.
(3) "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written
outside the range. The data have been expressed in the decimal notation. For writing the data through
the communication function, take the minimum setting unit into consideration, and use hexadecimal
system.
(4) "Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).
For example, the "minimum setup unit" of acceleration time (
For setting a data to 10 seconds, transmit 0x03E8 [10÷0.01=1000d=0x03E8] by communication.
(5) Communication numbers "0xxxxA" to "0xxxxF" don't exist in VF-MB1 or VF-S15.
Therefore, these communication numbers are skipped when read or write.
For example:
When the data of two words is read from acc(0009h), 0x000A doesn't exist because of this
specification.
Consequently, in this case ACC(0009h) and DEC(0010h) are read.
Adjustment range
Displays parameters in groups of
five in the reverse order to that in
which their settings were changed.
0 : -
1 : -
2 : Preset speed guidance
3 : Analog signal operation guidance
...
0 : -
1 : Constant torque characteristic
(150%-60s)
2 : Variable torque characteristic
(120%-60s)
0.1 to 6000 sec.
0 : -
1 : 50 Hz default setting
2 : 60 Hz default setting
3 : Default setting 1 (Initialization)
...
enables to set to 0.01 sec. (adjustment range: 0.01 - 600.0 sec.).
- 71 -
Minimum
setting unit
Default
Write during
(Panel/Communi
setting
running
-
cation)
1/1
-
1/1
0
Disabled
1/1
-
Disabled
0.1/0.1 *2
*1
Enabled
1/1
-
Disabled
) is 0.01, and 1 is equal to 0.01s.
E6581741
Refer
ence
-
4.3
5.1
4.3
5.2
3.5
5.3
6.14
5.2
5.20