Toshiba TOSVERT VF-MB1/S15 IPE002Z Function Manual page 9

For tosvert vf-mb1/s15
Hide thumbs Also See for TOSVERT VF-MB1/S15 IPE002Z:
Table of Contents

Advertisement

Communi
Title
cation No.
C021
Scanner output 1 address (*3)
c021
C022
Scanner output 2 address (*3)
c022
c023
C023
Scanner output 3 address (*3)
c024
C024
Scanner output 4 address (*3)
C025
Scanner output 5 address (*3)
c025
C026
Scanner output 6 address (*3)
c026
C081-
c081-
Device Name 1-16 (*4)
C096
c096
Communication error
C100
c100
detection delay time
Inverter operation at the
c101
C101
communication loss action
Preset speed operation
c102
C102
selection
Communication time-out
C103
c103
condition selection
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
(*4): (
) does not work for this parameter.
Function
0: -
1: fd01 (Status information 1)
2: fd00 (Output frequency, 0.01Hz)
3: fd03 (Output current, 0.01%)
4: fd05 (Output voltage, 0.01%)
5: fc91 (Alarm information)
6: fd22 (PID feedback value, 0.01Hz)
7: fd06 (Input terminal board status)
8: fd07 (Output terminal status)
9: fe36 (VIB input, 0.01%)
10: fe35 (VIA input, 0.01%)
11: fe37 (VIC input, 0.01%)
12: fd04 (Input voltage (DC detection), 0.01%)
13: fd16 (Estimated speed 0.01Hz)
14: fd18 (Torque, 0.01%)
15: -
16: -
17: -
18: -
19: f880 (Free notes)
20: fd29 (Input power, 0.01kW)
21: fd30 (Output power, 0.01kW)
22: fe14 (Cumulative operation time, hour)
23: fe40 (FM terminal output monitor, 0.01%)
24: -
25: fd20 (Torque current, 0.01%)
26: fd23 (Motor overload factor, 0.01%)
27: fd24 (Drive overload factor, 0.01%)
28: fd25 (PBR overload factor, %)
29: fd26 (Motor load factor, %)
30: fd27 (Drive load factor, %)
31: fe56 (Pulse train input, pps)
32: fe70 (Drive rated current, 0.1A)
33: fe76 (Input Watt-hour, 0.1kWh
34: fe77 (Output Watt-hour, 0.1kWh
35: fd83 (IGBT temperature, degree C)
0-35 (Same as c021)
0-35 (Same as c021)
0-35 (Same as c021)
0-35 (Same as c021)
0-35 (Same as c021)
16 characters
The device name is required if the card uses
DHCP to obtain its IP Address.
Refer to " 3.2.1 Device name (c081-c096) for the
details.
0.0 - 100.0 sec.
0: Stop and controlled by cmod, fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (err8 trip)
5: Preset speed operation (by c102 setting)
0: None
1 to 15: Preset speed
0: Disconnection detection
1: When communication mode enable (Both
cmod and fmod are set CANopen or
communication option) only
2: 1 + Driving operation
- 8 -
E6581741
Description
10
f749
10
f749
Factory
setting
1
)
)
2
0
0
0
0
0,0,0,0,
0,0,0,0
0.0
4
0
0