Dual Duct Pressure Independent Constant Volume Atu - Honeywell AUTOMATIC CONTROL SI Edition Engineering Manual

For commercial buildings
Table of Contents

Advertisement

The dotted line of F igure 10 shows a modification of this str ategy
wher ein the constant v olume r equir ement is r elaxed a little to
pr ovide some VAV cooling contr ol pr ior to g oing into the hea ting/
mixing por tion of contr ol. This allows a dead band and a little
VAV cooling contr ol. This uses the same har dwar e (and cost) and
allows an easil y adjusta ble minim um airf low, up to the maxim um.
In this conf igur ation, the r oom will oper ate at the hea ting setpoint
most of the time and the lo wer the minim um airf low is set, the
more time control will be in the deadband range or at the cooling
setpoint. Rooms ma y have either high minim um airf low setpoints
or low minim um airf low setpoints.
25.5
13
ENGINEERING MANUAL OF AUTOMATIC CONTROL
HOT
DUCT
COLD
DUCT
00
77
0.455
DAMPER
CURRENT
PERCENT
AIRFLOW
3
OPEN
(m
/s)
CONSTANT
AIRFLOW
SETPOINT
AIRFLOW
3
(m
/s)
ZERO
MAX
HEATING
LOAD
Fig. 11. Dual-Duct Constant Volume Air Terminal Unit.
INDIVIDUAL ROOM CONTROL APPLICATIONS
Dual Duct Pressure Independent
Constant Volume ATU
Figur e 11 shows a constant v olume pr essur e independent dual
duct ATU. Modula ting the hot duct damper , up to a total f low
not to exceed the maximum airflow setpoint maintains the room
temper atur e. A constant total airf low is nor mally maintained
by modula ting the cold duct damper . With this conf igur ation,
there is no deadband and comfort is maintained by mixing hot
and cold air a t a constant total airf low. Hot and cold duct
temper atur e load r eset is very impor tant in all dual duct systems
to minimiz e ener gy waste.
WALL MODULE
24
0.455
AIRFLOW
SETPOINT
3
(m
/s)
MAX
COOLING
LOAD
407
TEMPERATURE
COOLING
SETPOINT
24
M15312