SINGLE CENTRIFUGAL CHILLER CONTROL APPLICATION

FUNCTIONAL DESCRIPTION
TOWER
CONTROL
16
23
4
ON
14
ENABLED
BY REMOTE
CONTROLS
1
Item No.
Function
1
Indicates when chiller system is required by
fan system.
2
Chilled water pump ON-OFF-AUTO
function. In AUTO pump runs when fan
systems need chilled water.
3
Chiller ON-OFF-AUTO function (In ON and
AUTO chilled water flow required for chiller
to run).
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
CHILLED WATER SETPOINT
6.5
6
MINIMUM
CURRENT
13
6
CHILLER 1
26
AUTO
ON
OPERATING
STATUS
MODE
3
10
Fig. 9. Single Chiller Control Graphic.
9.5
MAXIMUM
7
5
100
NORMAL
78
PERCENT LOAD
ALARM
STATUS
MAX
CURRENT
11
8
15
CONTROL
PROGRAM
4
Condenser pump status. Pump started by
chiller controls when chilled water needed.
5,6
Chiller leaving water temperature and setpoint.
7
Icon to select chiller control dynamic
sequence display (Fig. 10).
8
BMCS commandable load limiting function.
9-14
Operator information.
15
Control program coordinates chiller control.
16
Icon to select cooling tower control displays.
303
CHILLER
SYSTEM
CONTROL
7
2
AUTO
10.5
9
12
M15253