DUAL CENTRIFUGAL CHILLERS CONTROL APPLICATION

FUNCTIONAL DESCRIPTION
MORNING LEAD
CHILLER SELECTOR
1
26
1 = CHILLER 1 LEADS
2 = CHILLER 2 LEADS
3 = ALTERNATES
12
TOWER
19
CONTROL
ON
4
13
1
32.5
ENABLED
BY REMOTE
CONTROLS
4
DISABLED
OFF
14
29.5
Item No.
Function
1
Indicates when chilled water is required by
fan system.
2
Chilled water pump ON-OFF-AUTO
function. In AUTO pump runs when system
needs chilled water.
3
Chiller ON-OFF-AUTO function (In ON and
AUTO chilled water flow required for chiller
to run).
4
Condenser pumps status. Pumps started by
chiller controls when chiller needed.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
CHILLED WATER SETPOINT
5.5
MINIMUM
9
SEQUENCES
CHILLER 1
3
15
ON
AUTO
OPERATING
STATUS
MODE
OFF
AUTO
CHILLER 2
Fig. 14. Dual Centrifugal Chiller Control Graphic.
6
8
10
MAXIMUM
CURRENT
7
CHILLER
CONTROL
SETPOINTS
5.5
5
11
17
78
100
NORMAL
8
PERCENT LOAD
ALARM
STATUS
MAX
CURRENT
100
00
NORMAL
13
5
5,6
Chiller leaving water temperature and setpoint.
7
Icon to select chilled water setpoint reset
dynamic sequence display (Fig. 15).
8
BMCS commandable load limiting functions.
9
Lead chiller selector function.
10-17
Operator information.
18
Control program coordinates chiller staging
and control.
19
Icon to select cooling tower control displays.
20
Icon to select chilled water flow and pressure
control displays.
307
18
20
FLOW &
PRESSURE
CONTROL
CONTROL
PROGRAM
2
5.6
AUTO
13
11
2
AUTO
M15255