Typical Damper Construction; Performance Data; Leakage Ratings - Honeywell AUTOMATIC CONTROL SI Edition Engineering Manual

For commercial buildings
Table of Contents

Advertisement

DAMPER SELECTION AND SIZING
DAMPER
Fig. 16. Baffle Inside Duct Surrounds Damper.

TYPICAL DAMPER CONSTRUCTION

Figure 17 shows construction of an opposed blade damper
with linkage. A parallel blade damper is essentially identical
except for placement of blade linkage and rotation direction of
alternate blades. Higher leakage dampers have either no blade
side seals or less effective sealing elements, e.g., adhesive-
backed cellular foam strips.

PERFORMANCE DATA

Performance data for dampers can vary in content and form
due to the many types of dampers and the philosophies of their
manufacturers. When casually compared, performance ratings
of different dampers may seem equivalent but are not due to
differences in criteria on which the data is based. The following
paragraphs discuss the types of performance data and their
variations.

LEAKAGE RATINGS

Leakage ratings of dampers are the most widely publicized
damper performance data. Figure 18 graphically shows typical
leakage performance of dampers with side seals, but without
blade edge seals. The torque necessary to achieve the indicated
leakage ratings is specified at the top of the graph as 6.0 Nm
per square meter of damper area. The wide performance band
is explained by the note at the bottom of the graph.
BAFFLE
M10418
For typical dampers, leakage increases more significantly with
the number of blades than with the length of the blades. The data
shown applies to a combination of damper heights and widths.
For example, a damper 1.22m high x 0.305m wide is the area
equivalent of a damper 0.305m. high x 1.22m wide. However,
there is significantly more leakage with the 1.2m high x 0.305m
wide damper, due to the increased number of blades. Using the
leakage performance graph in Figure 18, the range of leakage for
these two dampers (0.37 m
Leakage = Area x Rating/m
Minimum Leakage = 0.37 x 0.05 (min)
Maximum Leakage = 0.37 x 0.13 (max)
Performance characteristics for low leakage dampers differ
from standard dampers. Figure 19 shows typical pressure drop/
leakage rating relationship for low leakage dampers. Specific
leakage ratings for horizontal (A) and vertical (B) damper
dimensions are listed and the torque required has been increased
to a flat value for any single section to accommodate light
compression blade edge seals.
Using the leakage ratings in Figure 19, the leakage of the
two dampers in the previous example at 0.249 kPa is:
0.305m (A) + 1.22m (B) = 0.95 L/s + 20.5 L/s
If the A and B dimensions are reversed, the leakage is as
follows:
1.22m (A) + 0.305m (B) = 3.4 L/s + 6 L/s
Other methods of conveying leakage ratings are a tabular
format (e.g., leakage per area in m
percentage basis. The tabular format lists specific ratings for
each individual damper size. Leakage per area must include
sizes of interest. The percentage basis leakage rating is
meaningless unless complete conditions including total airflow
that the data is based on are also stated.
In many cases, damper data indicates that it is certified by an
industry association. Certification means that tests were done
under conditions defined by an association of manufacturers
but is not a rating by an approval body. For applications other
than smoke and fire, there are no approval bodies governing
damper leakage or any other performance characteristics.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
452
2
each) at 0.249 kPa is:
2
3
= 0.018 m
/s
3
= 0.47 m
/s
= 21.45 L/s
= 9.4 L/s
3
/s per square meter) and a

Advertisement

Table of Contents
loading

Table of Contents