SPECIFYING GRAPHICS (I/O SUMMARIES)

When writing the control sequence of operation, sketch the
graphic (Fig. 7) and note the necessary inputs and outputs
required for control. Develop an Input/Output (I/O) Summary
(Fig. 8) where, the X-axis lists generic types of points and the
ENGINEERING MANUAL OF AUTOMATIC CONTROL
100
33
26
COOLING
TOWER
CONTROL
CHILLED WATER SETPOINT
7
8
11
MINIMUM
ACTUAL
MAXIMUM
CHILLER 1
33
ON
100
AUTO
MAX
OPERATING
STATUS
MODE
CURRENT
AUTO
OFF
100
CHILLER 2
30
Fig. 7. Graphic Sketch for Sequence of Operation.
BUILDING MANAGEMENT SYSTEM FUNDAMENTALS
DUAL CHILLER PLANT
CONTROL
0
GRAPHIC DISPLAY
LEAD CHILLER
SELECTOR
1
1 = CHILLER 1 LEADS
2 = CHILLER 2 LEADS
PRESSURE
7
AUTO
78
NORMAL
%
ALARM
LOAD
STATUS
00
NORMAL
13
AUTO
Y-axis lists the specific points. Publishing the graphic sketch
with all hardware and software points and symbols is an
excellent alternative to the I/O summary.
193
PRESSURE BYPASS
& CHOKE VALVE
CONTROL
DUAL CHILLER
SETPOINT
REDUCTION
72.4
BYPASS
365
VALVE
00
365
7.3
PRESSURE
13.0
CHOKE
VALVE
CHILLER
CONTROL
SETPOINTS/
SEQUENCES
kPa
100
TO
AHUs