Heating, Cooling, Humidification, And Dehumidification Control Without Dead-Bands - Honeywell AUTOMATIC CONTROL SI Edition Engineering Manual

For commercial buildings
Table of Contents

Advertisement

AIR HANDLING SYSTEM CONTROL APPLICATIONS
HEATING, COOLING, HUMIDIFICATION, AND DEHUMIDIFICATION CONTROL
WITHOUT DEAD-BANDS
Functional Description
EA
N.C.
83
5
NORMAL
N.O.
OA
N.C.
9
7
PERCENT
83
9
OPEN
16
4
28
ECONOMIZER DECISION.
REFER TO PREVIOUS
ECONOMIZER OPTIONS
8
6
22
OA MINIMUM SETPOINT
(NOTE: THE TEST AND
BALANCE INITIAL
VALUE FOR PROPER
VENTILATION IS 22)
Item
No.
Function
1-3
Control system energizes when fan is turned
on (See FAN SYSTEM START-STOP
CONTROL).
4-6
Manual positioning value determines
minimum ventilation mixing damper position.
7
Operator information, outdoor air temperature.
8
Economizer enables free cooling when OA is
suitable.
9
Operator information, MA temperature.
10,27
Heating coil valve modulates to keep reheat
coil entering air from getting too low.
11-16
Space temperature PI loop resets setpoint of
reheat coil SA PI loop to maintain constant
space temperature.
RA
ON
3
2
10
18
13
27
0
100
CONTROL
PROGRAM
24
52
SA
88
25
13.5
16
1
ON
15
SUPPLY
FAN
26
11
0
17,18
Chilled water valve modulates in sequence
with mixing dampers as required to maintain
SA PI setpoint.
19
Chilled water coil leaving air temperature
lowered if required for dehumidification.
20-26
Space humidity PI control loop modulates
humidifier valve to maintain space relative
humidity, subject to an SA high limit
humidity PI loop.
27
Control program coordinates ventilation,
heating, cooling, humidification,
dehumidification, and fan interlocks.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
252
52
20
21
50
SPACE
23.5
11
12
23.5
SUPPLY AIR
TEMPERATURE
COOLING
SETPOINT
DEMAND
41
REHEAT
14
13
40
45
24
OA
CW
13
100
17
COOL COIL
LEAVING AIR
HUMIDI-
TEMPERATURE
FICATION
SETPOINT
DEMAND
13
0
19
21
45
HUMIDIFIER
VALVE POSITION
0
55
23
100
100
35
13
0
50
22
M15180