Chapter 4 Rack and Optional Product Installation
4.2 Installable Racks
Rack front door
Figure 4.1
Table 4.2
(1)
(2)
(3)
(4)
Placement conditions
When determining service areas, refer to the installation document of the rack to be used.
Install air conditioning in order to ensure that the interior temperature of the rack satisfies the
temperature conditions listed in
Conditioning" (page
ETERNUS DX60 S2 Disk storage system User's Guide -Site Planning-
(1)
ETERNUS DX
Disk storage system
(4)
Rack pillars
Unit installation area
Specifications for the unit installation area
Specification
Rack front space
(From the fixed part of the ETERNUS DX Disk storage
system on the front side to the inner side of the front
rack door)
Mount bracket length
(Size between each end of the front and rear rack
pillars)
Rack space
(From the fixed part of the ETERNUS DX Disk storage
system on the front side to the inner side of the rear
rack door)
Rack mount kit installation area
"2.1 Installation Specifications" (page 26)
30).
55
Copyright 2012 FUJITSU LIMITED
(2)
(3)
Rack rear door
40mm or more
630mm to 800mm
830mm or more
482mm or more (recommended)
Rack rails
Condition
and
"2.4.1 Air
P3AM-5492-04ENZ0