Chapter 2 ETERNUS DX Disk Storage System Installation
2.6 Circuit Protectors
For direct (no power distribution unit) connection
The breaking characteristics of distribution board circuit protectors must be slower than the val-
ues shown in
1000
100
10
0.1
0.01
0.001
Figure 2.8
Table 2.12
Delay
200E
Figure 2.9
ETERNUS DX60 S2 Disk storage system User's Guide -Site Planning-
Figure 2.8
or equivalent to D (IEC898).
CURVE 200E
1
100
200
300
400
125
PERCENT LOAD (%)
150
ETERNUS DX Disk storage system (PSU) breaking characteristics (graph)
ETERNUS DX Disk storage system (PSU) breaking characteristics (Trip time (sec.))
100%
125%
No Trip
45 to
500
ETERNUS DX Disk storage system
P
S
CP
U
Line 0
Example of a power supply connection without power distribution units
Do
CAUTION
Only connect the ETERNUS DX Disk storage system to circuit
protectors.
Copyright 2012 FUJITSU LIMITED
500
600
700
800
900
150%
200%
400%
15 to
6 to
0.7 to
250
90
P
S
DE #01
U
CE
Line 1
CP: Circuit Protector
40
1000
600%
800%
0.008 to
0.006 to
15
5
0.4
CP
P3AM-5492-04ENZ0
1000%
0.004 to
0.08