Figure 47 Unit Installation Area; Table 31 Specifications For The Unit Installation Area - Fujitsu ETERNUS AX Series Manual

Hide thumbs Also See for ETERNUS AX Series:
Table of Contents

Advertisement

2.
Rack Installation Specifications
Installable Racks
Figure 47
Unit Installation Area
Top
Front door of the rack
Table 31
Specifications for the Unit Installation Area
(1)
Rack front space
(Space between the fixed part of the ETERNUS AX/HX on
the front side and the front of the rack)
(2)
Mount bracket length
(Size between each end of the front and rear rack pillars)
(3)
Rack space
(Space between the fixed part of the ETERNUS AX/HX on
the front side and the rear of the rack)
(4)
Rack mount kit installation area
*1:
For the DS460C, the recommended depth of the rack space is equal to the depth of the shelf body (922 mm) + 60
mm or more because the cable connection interface has depth of 40 mm from the rear surface of the shelf.
Installation Requirements
When determining service areas, refer to the manual of the rack that is to be used.
Be sure to perform the installation according to the requirements described in
9)
and
"Installation Environment" (page
(1)
(2)
ETERNUS
(4)
Rack pillars
Specification
30).
66
(3)
Rack rails
Rear door of the rack
50 mm or more
600 mm to 790 mm
The depth of the shelf body (*1) + 100 mm or
more (recommended for the extra cable
length)
483 mm or more (recommended)
"Installation Specifications" (page
Condition
Site Planning Guide