Figure 2.7 Example Of A Power Supply Connection Using A Power Distribution Unit (1U); Table 2.11 Power Distribution Unit (1U) Breaking Characteristics (Trip Time (Sec.)) - Fujitsu ETERNUS DX60 S2 User Manual

Disk storage system
Hide thumbs Also See for ETERNUS DX60 S2:
Table of Contents

Advertisement

Chapter 2 ETERNUS DX Disk Storage System Installation
2.6 Circuit Protectors
Table 2.11
Delay
200E
Line 0
To power supply facility
Figure 2.7
ETERNUS DX60 S2 Disk storage system User's Guide -Site Planning-
Power distribution unit (1U) breaking characteristics (Trip time (sec.))
100%
125%
No Trip
45 to
500
ETERNUS DX Disk storage system
DE #01
CE
CP
CP
Power distribution unit
CP
Distribution
board
To power supply facility
Example of a power supply connection using a power distribution unit (1U)
Copyright 2012 FUJITSU LIMITED
150%
200%
400%
15 to
6 to
0.7 to
250
90
15
Line 1
CP
Distribution
board
CP: Circuit Protector
39
600%
800%
1000%
0.008 to
0.006 to
0.004 to
5
0.4
0.08