Figure 19 Unit Installation Area; Table 20 Specifications For The Unit Installation Area - Fujitsu ETERNUS AF250 S2 Site Planning Manual

Hide thumbs Also See for ETERNUS AF250 S2:
Table of Contents

Advertisement

2.
Rack Installation Specifications
Installable Racks

Figure 19 Unit Installation Area

Front door of the rack

Table 20 Specifications for the Unit Installation Area

Specification
(1)
Rack front space
(Space between the fixed part of the ETERNUS AF on the
front side and the front of the rack)
(2)
Mount bracket length
(Size between each end of the front and rear rack pillars)
(3)
Rack space
(Space between the fixed part of the ETERNUS AF on the
front side and the rear of the rack)
(4)
Rack mount kit installation area
Placement Requirements
When determining service areas, refer to the manual of the rack that is to be used.
Make sure to perform the installation according to the placement requirements described in
cations" (page 7)
(1)
(2)
ETERNUS AF
(4)
Rack pillars
and
"Installation Environment" (page
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays Site Planning Guide
Copyright 2021 FUJITSU LIMITED
(3)
Rack rails
Rear door of the rack
Condition
40mm or more
685mm or more
775mm or less
830mm or more
482mm or more
(recommended)
16).
36
"Installation Specifi-
P3AG-1812-06ENZ0