Chapter 2 ETERNUS DX Disk Storage System Installation
2.6 Circuit Protectors
2.6.2

Breaking Characteristics

For power distribution unit (2U) connection
The breaking characteristics (*1) of distribution board circuit protectors must be slower than the
values shown in
*1:
Relationship between the size of excess current and operation time
10000
1000
100
10
1
.1
.01
.001
Figure 2.4
Table 2.10
Delay
63
ETERNUS DX60 S2 Disk storage system User's Guide -Site Planning-
Figure 2.4
or equivalent to D (IEC898).
0
100
150
200
300
400
125
PERCENT OF RATED CURRENT
Power distribution unit (2U) breaking characteristics (graph)
Power distribution unit (2U) breaking characteristics (Trip time (sec.))
100%
125%
No Trip
50 to
700
Copyright 2012 FUJITSU LIMITED
DELAY 63
500
600
700
800
900
150%
200%
400%
30 to
10 to
1.5 to
400
150
37
1000
600%
800%
0.4 to
0.013 to
20
10
0.85
P3AM-5492-04ENZ0
1000%
0.013 to
0.5