Setup System - Setup Outputs

The AC8 has eight outputs that may be configured individually. These outputs correspond to the
eight numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1.
The output name is the same as the input name, as described in 7.3.1 -
Change Label (Name of Input).
To configure an output:
Log In and Choose Setup System
• From the Main Menu, use the arrows
Control, then press Enter
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
Setup System, then press Enter .
Select an Output to Configure
• From the Setup System Menu, shown at right, use the arrows
choose Setup Outputs and press Enter .
• From the Select Output Menu, choose an output—for example,
Device_1—and press Enter .
Table 19 shows digital output features and their default settings: you
may define an output as Normally Open or Normally Closed, set the
device's mode—operating, standby or not used—and specify whether to
disable the device during emergency power operation.
Use the steps following Table 19 to change the default settings for any
digital output.
Table 19
Default settings - digital outputs
Feature
NORM OPEN/CLOSE
MODE*
IN ALARM
EMERG OP
* Outputs defined as Not Used should be kept in a separate zone that does not include
any outputs defined as Operating or Standby. The Auto Sequencing feature will not
function properly in a zone with outputs defined as Not Used. See 7.10.1 - Turn
Automatic Sequencing On or Off for more information.
7.7.1

Define Output as Normally Open or Normally Closed

Each output may be set up as Normally Open (NO) or Normally Closed
(NC). The default setting for all output points is NO (Normally Open).
• From the Setup Outputs Menu, shown at right, use the arrows
to choose Norm Open/Close and press Enter .
• To change the normal state for this output, use the arrows
choose the state:
• NO (Normally Open)
• NC (Normally Closed)
• Press Enter .
to choose System and
(see 7.1 - Login for help)
Default
NO (Normally Open)
Outputs 1-2:
OP (Operating)
Outputs 3-4:
ST (Standby)
Outputs 5-8:
NU (Not Used)
E (Enable)
E (Enable)
47
Setup System Menu
> SETUP OUTPUTS
to choose
Select Output Menu
to
> DEVICE_1
Other Options
NC (Normally Closed)
OP (Operating)
ST (Standby)
NU (Not Used)
D (Disable)
D (Disable)
Setup Outputs Menu
> NORM OPEN/CLOSE: NO
to
Change State
SET TO NORMAL OPEN
OR NORMAL CLOSE? NO
System and Control Options
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
=NEXT
=SELECT
SETUP ZONES
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
SELECT OUTPUT
NO-OP-E-E
DEVICE_2
NO-ST-E-E
=NEXT
=SELECT
DEVICE_3
NO-ST-E-E
DEVICE_4
NO-ST-E-E
DEVICE_5
NO-NU-E-E
DEVICE_6
NO-NU-E-E
DEVICE_7
NO-NU-E-E
DEVICE_8
NO-NU-E-E
SETUP DEVICE_1
MODE: OPERATING
=NEXT
=SELECT
IN ALARM: ENABLE
EMERG OP: ENABLE
=NO/NC
=END