Emerson Autochangeover Controllers AC8 User Manual page 70

Emerson autochangeover controllers owner manual
Table of Contents

Advertisement

Upload the Configuration File
13. At the prompt to Initiate an Upload of Configuration File, enter Y (Yes - begin) or N (No - cancel).
The current setting appears in brackets—[N] in the following example.
>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)?
>[N]
>[
NOTE
The following instructions refer to the Microsoft Windows HyperTerminal program. These
steps may vary for other communications programs.
14. At the top of the HyperTerminal window, shown below, click on Transfer, then on Send File.
15. In the Send File window, as shown above:
• In the Filename box, enter the full path of the file to be uploaded—for example,
C:\ac8_conf.sav—or click on the Browse button to locate the file.
• In the Protocol box, select Xmodem from the drop-down list.
• Click on the Send button. (To close the window without sending the file, click on Close or
Cancel.)
16. When the transfer is complete, a confirmation message—"Upload Successful"—appears in the
Service Terminal Interface window and the AC8 reboots with the new configuration.
62
System and Control Options
Enter filename -
for example,
ac8_conf.sav
Select Xmodem
Send button