Facility Requirements
Power Specifications
Specifications
Table 11. Component Weights
Component
CP Card
16-Port Card
Card Filler Panel
Cable Management Tray
To ensure correct operation of the switch, the facility where the switch is
used must meet the following requirements:
• Input Power Requirements: 200-240 VAC, 12A, 50-60 Hz.
• Adequate supply circuit, line fusing, and wire size, as specified by the
electrical rating on the chassis nameplate.
• An air flow of at least 350 cubic feet per minute, available in the
immediate vicinity of the switch.
• The power specifications listed in
• The environmental specifications listed in
• The electrical interference must be less than the levels stated in the
standards listed under
• When the switch is installed in a rack:
– All equipment installed in the rack should have a reliable branch
circuit ground connection, and should not rely on a connection to a
branch circuit, such as a power strip.
– The rack should be balanced and the installed equipment within the
rack's weight limits. Ensure the rack is mechanically secured to
insure stability in the event of an earthquake.
System can operate with any of three phases of a three-phase or
Note
single-phase power utility installation.
Value
5.6 pounds (2.5 kg)
8.6 pounds (3.9 kg)
3.2 pounds (1.6 kg)
0.6 pounds (0.27 kg)
Table 12
Table 13
"Immunity"
in
Table 14
on
page
72.
on
page
73.
on
page
74.
71