Facility Requirements
To ensure correct operation of the switch, the facility where the switch is in use
must meet the following requirements shown in
Table 18: Facility Requirements
Type
Electrical
Thermal
Cabinet (when
rack-mounted)
SAN Switch 2/8V, 2/16V and 2/16N Installation Guide
Primary AC Input 100-240 VAC, 1.5A, 47-63 Hz (SAN Switch 2/8V)
and 100-240 VAC, 2.0A, 47-63 Hz (SAN Switch 2/16V); switch
autosenses input voltage
Adequate supply circuit, line fusing, and wire size, as specified by the
electrical rating on the switch nameplate
Circuit protected by a circuit breaker and grounded in accordance with
local electrical codes
See
Table 20
on page 98 for details
A minimum air flow of 24 cubic ft/minute available in the immediate
vicinity of the switch
Ambient air temperature not exceeding 40 C (104 F) while the
switch is operating
One rack unit in a 19-in. (48.3 cm.) cabinet
All equipment in cabinet grounded through a reliable branch circuit
connection
Additional weight of switch must not exceed the cabinet's weight limits
Cabinet must be secured to insure stability in case of unexpected
movement, such as an earthquake
Table
Requirements
Technical Specifications
18:
95