Table 1-4: Technical Information - Eaton Cutler-Hammer SPI9000 User Manual

Inverter unit fi9 – fi14
Table of Contents

Advertisement

SPI9000 Inverter Unit FI9 – FI14 User Manual

Table 1-4: Technical Information

Description
Supply Connection
Input Voltage V
Input Current I
DC Bank Capacitance
Starting Delay
Motor Connection
Output Voltage
Continuous Output Current
Starting Torque
Peak Current
Output Frequency
Frequency Resolution
Control Characteristics
Control Method
Switching Frequency
(See Parameter 2.6.9)
Frequency Reference
Analog Input
Panel Reference
Field Weakening Point
Acceleration Time
Deceleration Time
Braking Torque
Ambient Conditions
Ambient Operating Temperature -10°C (no frost) to +40°C: I
Storage Temperature
Relative Humidity
Air Quality:
– Chemical Vapors
– Mechanical Particles
Altitude
1-6
Specification
465 – 800V DC; 380 – 500V AC (-0%. to +0%)
in
640 – 1100V DC; 525 – 690V AC (-0% to +0%)
The waviness of the inverter supply voltage, which is formed in
rectification of the electric network's alternating voltage in basic
frequency, must be less than 50V peak-to-peak.
(sqrt3 x U
in
FI9 380 – 500V: 4950 μF; FI9 525 – 690V: 3733 μF
FI10 380 – 500V: 9900 μF; FI10 525 – 690V: 7467 μF
FI12 380 – 500V: 19800 μF; FI12 525 – 690V: 14933 μF
FI13 380 – 500V: 29700 μF; FI13 525 – 690V: 22400 μF
5 seconds (FI9 and greater)
3 ~ 0 – V
I
: Ambient temperature max. +50°C,
H
overload 1.5 x I
I
: Ambient temperature max. +40°C,
L
overload 1.1 x I
I
for two seconds (torque motor dependent)
S
I
for 2 seconds every 20 seconds
S
0 – 320 Hz; 7200 Hz (special)
Application dependent
Frequency control V/f
Open loop: Sensorless vector control
Closed loop: Frequency control
Closed loop: Vector control
380 – 500V, 1 – 10 kHz; Factory default 3.6 kHz
525 – 690V, 1 – 6 kHz; Factory default 1.5 kHz
Resolution 0.1% (10 bits); Accuracy ±1%
Resolution 0.01 Hz
30 – 320 Hz
0 – 3000 sec
0 – 3000 sec
DC brake: 30% * T
-10°C (no frost) to +40°C: I
-40 to 158°F (-40 to 70°C)
0 – 95% RH, non-condensing, non-corrosive,
no dripping water
IEC 721-3-3, unit in operation, Class 3C2
IEC 721-3-3, unit in operation, Class 3S2
100% load capacity (no derating) up to 1,000m
1% derating for each 100m above 1000 (maximum, 3000m)
For more information visit: www.EatonElectrical.com
x I
x cosϕ) / (V
x 0.98)
mot
mot
in
/ 1.4
in
(1 min./10 min.)
H
(1 min./10 min.)
L
(without brake)
N
H
L
September 2006
MN04004002E

Advertisement

Table of Contents