Table 3-4: Cable Sizes For 380 – 500V Ac - Eaton Cutler-Hammer SPI9000 User Manual

Inverter unit fi9 – fi14
Table of Contents

Advertisement

September 2006
Inverter Supply and Motor Cables — 380 – 500V AC
Table 3-4: Cable Sizes for 380 – 500V AC
Nominal
Current
140
170
205
245
300
385
460
520
590
650
730
820
920
1030
1150
1300
1600
1940
2300
Flexible conductor. Minimum temperature endurance for isolation 70°C.
Copper busbar.
The modules require symmetrical parallel cable with minimum length 40m or dU/dt- or sinus filter.
Table valid for enclosure class IP20 cabinets.
Motor cables — EN 60204-1, IEC 60364-5-2/2001
PVC insulation
40°C ambient temperature
70°C surface temperature
MN04004002E
Frame
I
[A]
L
FI9
170
205
261
300
FI10
385
460
520
FI12
590
650
730
820
920
1030
FI13
1150
1300
1450
FI14
1770
2150
2700
For more information visit: www.EatonElectrical.com
SPI9000 Inverter Unit FI9 – FI14 User Manual
Module Supply (DC)
2
(per terminal Cu [mm
]
2x(1x24)
2x(1x24)
3x(1x24)
6x(1x24)
5x40
5x40
6x40
5x40
5x40
5x40
5x40
5x40
6x40
5x40
5x40
6x40
5x40
5x40
6x40
Motor Cable
2
[mm
]
Cu: 3x95+50
Al: 3x120+70
Cu: 3x150+70
Al: 3x240Al+72Cu
Cu: 3x185+95
Al: 2x(3x120+70)
Cu: 2x(3x120+70)
Al: 2x(3x185Al+57Cu)
Cu: 2x(3x120+70)
Al: 2x(3x185Al+57Cu)
Cu: 2x(3x150+70)
Al: 2x(3x240Al+72Cu)
Cu: 2x(3x185+95)
Al: 2x(3x300Al+88Cu)
Cu: 2x(3x240+120)
Al: 4x(3x120Al+41Cu)
Cu: 4x(3x95+50)
Al: 4x(3x150Al+41Cu)
Cu: 4x(3x120+70)
Al: 4x(3x185Al+57Cu)
Cu: 4x(3x150+70)
Al: 4x(3x185Al+57Cu)
Cu: 4x(3x150+70)
Al: 4x(3x240Al+72Cu)
Cu: 4x(3x185+95)
Al: 4x(3x300Al+88Cu)
Cu: 4x(3x240+170)
Al: 6x (3x185Al+57Cu)
Cu: 6x(3x150+70)
Al: 6x (3x240Al+70Cu)
Cu: 6x(3x185+95)
Al: 6x (3x240Al+70Cu)
Cu: 2x 4x(3x240+170)
Al: 2x 6x (3x185Al+57Cu)
Cu: 2x 6x(3x150+70)
Al: 2x 6x (3x240Al+70Cu)
Cu: 2x 6x(3x185+95)
Al: 2x 6x (3x240Al+70Cu)
3-11