SPI9000 Inverter Unit FI9 – FI14 User Manual

Table 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13)

Inverters
SPI820 – H10 480V

Fan Cooling

Frames FI9 to FI14
Enough free space must be left around the inverter to ensure sufficient air circulation and
cooling. You will find the required dimensions for free space Table 2-5.
If several units are mounted on top of each other, the required free space equals 2 * C (see
Figure 2-5). Moreover, the outlet air used for cooling by the lower unit must be directed away
from the air intake of the upper unit. When planning the cooling for the space, take into
consideration that the inverter's heat loss is 2.5% of the nominal capacity.
2-4
D1
Side
Dia.
Bottom

Figure 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13)

Approximate Dimensions in Inches (mm)
Voltage
W1
W2
H1
27.9
26.7
41.5
(708)
(677)
(1055)
For more information visit: www.EatonElectrical.com
W1
W2
Front
D2
D3
D5
D4
D3
Top
H2
H3
D1
D2
37.4
2.46
22.3
1.1
(950)
(62.5)
(566)
(27)
September 2006
H1
H2
H3
D3
D4
D5
Dia.
1.6
9.6
5.9
.37
(40)
(245)
(150)
(9.5)
MN04004002E