Power Xpert Solar 1500/1670 Kw Inverter; Product Description; Product Information And Labeling; Figure 3. Power Xpert Solar Inverter Rating Label (Typical) - Eaton Power Xpert Solar 1500 User Manua

Utility-scale photovoltaic inverter
Table of Contents

Advertisement

Power Xpert Solar 1500/1670 kW Inverter

Product Description

The Power Xpert Solar 1500/1670 kW Inverter is designed
for commercial and utility-scale photovoltaic systems.
Engineered for ease-of-installation, operation and
maintenance, the inverter contains the intelligence to
facilitate the commissioning, operation and shut-down
procedures. The inverter is based upon proprietary Eaton
technology, algorithms, and software.
The Power Xpert Solar 1500/1670 kW Inverter is designed
specifically for North American, 60-Hertz, 3-phase grid tie
applications and 1000 Vdc (array Voc) photovoltaic modules
and systems. The medium voltage level must be defined
when ordering.
Power Xpert Solar 1500/1670 kW Inverter MN141001EN—October 2014 www.eaton.com
Power Xpert Solar 1500/1670 kW Inverter

Product Information and Labeling

Complete inverter specifications are listed in Appendix A.
The most up-to-date inverter information and documentation
is available on the internet.
Navigate to: www.eaton.com/PowerXpertSolar
On the front of the inverter, near the Rating Label is the unit
general order number (GO#) and the serial number. Please
use this identification when contacting Eaton regarding your
inverter.
The Rating label attached to the inverter will be specific to
the unit and its assembly location (i.e., USA or Canada).
Figure 3. Power Xpert Solar Inverter Rating Label
(Typical)
Power Xpert™ Solar
1500 kW Inverter
Maximum Continuous Output Power AC (kW)
Maximum Input Voltage Open Circuit, (Vdc)
Maximum DC Input Operating Range (Vdc)
Maximum Peak Power Tracking Range, MPPT, (Vdc)
Nominal Output Current AC (A)
Maximum Branch Circuit Over Protection AC (A)
Nominal DC Operating Current DC (A)
Maximum Array Short Circuit Current DC (A)
Nominal Operating Voltage (Vac)
Operating Voltage Range (Vac)
Nominal Operating Frequency (Hz)
Enclosure Rating
Operating Temperature Range (°C)
Power Factor (Leading-Lagging)
Model No: Power Xpert Solar 1500
Eaton Corporation
Electrical Sector
877-ETN-CARE (877-386-2273)
30-46871-02
®
1500
1000
500 - 1000
500 - 1000
2700
3200
3100
5600
3-Ø, 320
288 to 352
60
UL Type 3R
-20 to 50
0.91 - 1.0
Conforms to UL STD 1741
Certified to CSA C22.2 No. 107.1-01
4003986
PHOTOVOLTAIC UTIILITY INTERACTIVE INVERTER
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert solar 1670

Table of Contents