NM-AIC-64, Contact Closure NetworkConfiguration Examples
!
dial-peer cor custom
!
line con 0
exec-timeout 0 0
transport input none
line 33
no exec
transport preferred none
transport input telnet
transport output none
stopbits 1
line aux 0
line vty 0 4
password lab
login
!
no scheduler allocate
!
end

AIC CLI Configuration for Alarms

These examples are output from the show alarm config # command.

Discrete Alarm

description:west door
normally closed
normal state description:door closed
alarm state description:door open
SNMP trap:enabled

Analog Alarm Monitoring Current

description:thermostat
high-high state description:very hot
high state description:hot
normal state description:just right
low state description:cold
low-low state description:very cold
current-loop -5.2 5.4 15.0 25.0 35.1 45.6
SNMP trap:enabled

Analog Alarm Monitoring Current Configured as a Discrete

description:east door
configured as discrete
normal state description:door closed
alarm description:door open
current-loop 0.0 3.2 5.9
SNMP trap:enabled