System Monitor Screens
Code
Description
80
Step Ladder Program
command error
81
Step Ladder Program
source designation not
defined
89
Overuse of Step
Ladder Program
differentiated
instruction

3-14-4 Data Link Status

Displays data link participation
status. (See note 2.) (1 bit per node.)
Explanation
There is an irrelevant
command in the Step
Ladder Program, or the
method of use of
commands is wrong, for
example, there is an AND
command even though
there is no input command.
Either the function block is
not registered to the block
address currently specified
by each command in the
Step Ladder Program, or
the ITEM number does not
exist.
The number of
differentiated instructions
to be simultaneously
executed has exceeded
256.
If using a Controller Link connection, you can display the Controller Link Net-
work's data link status.
Click the DTL Button.
The Data Link Status Dialog Box will be displayed.
Operation at Error
The command in question
and onwards are not
executed.
The command in question
and onwards are not
executed.
Differentiated instructions
exceeding 256 instructions
are not executed.
Click here.
Displays the data link status. (See note
1.) (8-bit 2-digit hexadecimal per node.)
Section
3-14
Remedy
Check the program within
the Step Ladder Program
block.
Check the block address
and ITEM number.
Reduce the number of
differentiated instructions
to be executed
simultaneously.
75