CHAPTER 3 BASIC OPERATION
3.6 Starting and Stopping Operation
F Manipulated vari-
able at stop
Setting Example
1 second min.
3--14
• You can start and stop operation by changing the setting of the "run/
stop" parameter (level 0 mode).
• You can switch the RUN/STOP function up to 100,000 times.
• To stop operation, set the "run/stop" parameter to [
a stop state, the "STOP" LED lights.
• Operation cannot be stopped during auto-tuning.
• Specify the manipulated variable (-5.0 to 105.0%) in the "MV at stop"
parameter (level 2 mode) to output the manipulated variable during
stop.
Factory-set to "0.0 : 0.0%"
The following example describes the procedure to follow to stop control
during operation of the controller.
(1) Select the menu display, and select [
or
keys. For details on selecting the menu display, see page
1-7.
(2) Press the
key for one second minimum to enter the level 0
mode. The PV and SP are displayed.
(3) Press the
key until [
played.
(4) Press the
key to select [
lights, and operation stops.
To resume operation, follow the above procedure to select [
("run"). The "STOP" LED goes out and operation starts.
] (level 0 mode) using the
] ("run/stop" parameter) is dis-
] (stop). The "STOP" LED
] (stop). In
]