AT hysteresis
• Usually Use the default value.
• The levels of limit cycle operations during AT execution are given hysteresis at
event ON/OFF switching. This parameter sets this hysteresis width.
Function
Setting Range
Comment
LBA detection width
• This parameter can be used when LBA is assigned as an output.
• When the change width of the manipulated variable is below the width set in this
parameter, the controller regards this as detection of an LBA.
Function
Setting Range
0.0 to 999.9
Comment
Unit
0.1 to 9.9
%FS
Unit
%FS
Expansion Mode
Conditions of Use
The control must be 2-PID control.
Default
0.2
Conditions of Use
The LBA (Loop Break Alarm) function
must be assigned as an output.
Default
0.2
5--35