Installation; Mounting - Omron E5 Getting Started Manual

Digital temperature controllers
Hide thumbs Also See for E5:
Table of Contents

Advertisement

Installation

2-1

Installation

2-1-1

Mounting

E5CN/CN-U
E53-COV17
Terminal Cover
Waterproof packing
1,2,3...
20
Adapter
Panel
E5CN
For the Wiring Socket for the E5CN-U, order the P2CF-11 or P3GA-11 sepa-
rately.
Mounting to the Panel
1. For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting several
Controllers. Waterproof packing is not necessary when there is no need for
the waterproofing function. There is no waterproof packing included with
the E5CN-U.
2. Insert the E5CN/E5CN-U into the mounting hole in the panel.
3. Push the adapter from the terminals up to the panel, and temporarily fasten
the E5CN/E5CN-U.
4. Tighten the two fastening screws on the adapter. Alternately tighten the
two screws little by little to maintain a balance. Tighten the screws to a
torque of 0.29 to 0.39 N·m.
Mounting the Terminal Cover
For the E5CN, make sure that the "UP" mark is facing up, and then attach the
E53-COV17 Terminal Cover to the holes on the top and bottom of the Temper-
ature Controller.