Executing Heating/Cooling Control
4-4-2

Settings

Setting Heating/Cooling Control
Operating Procedure
Initial Setting Level
Standard or
s-hc
Heating/
Cooling
stnd
Setting the Cooling Coefficient
Operating Procedure
Adjustment Level
Cooling
c-sc
Coefficient
1.00
c-sc
10.00
Setting the Dead Band
Operating Procedure
Adjustment Level
Dead Band
C
c-db
0.0
C
c-db
5.0
oscillating waves. If that occurs, increase the proportional band or the cooling
coefficient to improve control.
To set heating/cooling control, set the Standard or Heating/Cooling, Dead
Band, and Cooling Coefficient parameters.
Standard or heating/cooling = Heating/cooling
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select "heating/cooling control" in the initial setting level.
stnd: Standard control
h-c:
Heating/cooling control
Cooling Coefficient = 10
1. Select the Cooling Coefficient parameter in the adjustment level.
2. Use the U Key to set the parameter to 10.00.
Dead Band = 5
1. Select the Dead Band parameter in the adjustment level.
2. Use the U Key to set the parameter to 5.0.