Shifting Input Values
Infrared Temperature
Sensor
Power supply
Figure 1 Offset Configuration for an Infrared Temperature Sensor
Method for a 1-point Shift
1,2,3...
Upper-limit
C
insh
Temperature
Input Shift
10.0
Value
Lower-limit
C
insl
Temperature
Input Shift
10.0
Value
66
Output
1. In the configuration shown in Figure 1, bring the set point to near the value
at which the temperature of the control target is to be controlled. Assume
that the control target temperature (C) and the thermometer temperature
(B) are the same.
2. Check the thermometer temperature (B) and the Controller readout (A).
Subtract the Controller readout temperature (A) from the thermometer
temperature (B), and set insl and insh to the result as the input shift val-
ue. The shift is illustrated in Figure 2.
3. After setting the input shift values, check the Controller readout (A) and the
thermometer temperature (B). If they are almost the same, this completes
shifting the temperature input.
Controller readout (A)
Controller readout after
shifting (e.g., 120°C)
Controller readout before
shifting (e.g., 110°C)
Figure 2 Illustration of 1-Point Shift
(A) E5CN/AN/EN Temperature Controller
After shifting
Input shift value (e.g., 10°C)
Before shifting
0
Near set point
(e.g., 120°C)
Section 4-1
(C) Control target
(B) Thermometer
Control target temperature (B)