Setting the Input Type
List of Input Types
Input type
Controllers
Platinum resistance
with Ther-
thermometer
mocouple/
Resistance
Thermome-
ter Multi-
input
Thermocouple
Infrared temperature
sensor ES1B
Analog input
Thermocouple
Input type
Models with
Current input
analog
input
Voltage input
Specifications
Set value
Pt100
0
1
2
JPt100
3
4
K
5
6
J
7
8
T
9
10
E
11
L
12
U
13
14
N
15
R
16
S
17
B
18
10 to 70°C
19
60 to 120°C
20
115 to 165°C
21
140 to 260°C
22
0 to 50 mV
23
W
24
PLII
25
• The default is 5.
• If a platinum resistance thermometer is mistakenly connected while a set-
ting for other than a platinum resistance thermometer is in effect, S.ERR
will be displayed. To clear the S.ERR display, check the wiring and then
turn the power OFF and back ON. Make sure that the setting of the input
type parameter agrees with the sensor that is connected.
Specifications
Set value
4 to 20 mA
0
0 to 20 mA
1
1 to 5 V
2
0 to 5 V
3
0 to 10 V
4
• The default is 0.
Input temperature setting range
−200 to 850 (°C)/−300 to 1,500 (°F)
−199.9 to 500.0 (°C)/−199.9 to 900.0 (°F)
0.0 to 100.0 (°C)/0.0 to 210.0 (°F)
−199.9 to 500.0 (°C)/−199.9 to 900.0 (°F)
0.0 to 100.0 (°C)/0.0 to 210.0 (°F)
−200 to 1,300 (°C)/−300 to 2,300 (°F)
−20.0 to 500.0 (°C)/0.0 to 900.0 (°F)
−100 to 850 (°C)/−100 to 1,500 (°F)
−20.0 to 400.0 (°C)/0.0 to 750.0 (°F)
−200 to 400 (°C)/−300 to 700 (°F)
−199.9 to 400.0 (°C)/−199.9 to 700.0 (°F)
−200 to 600 (°C)/−300 to 1,100 (°F)
−100 to 850 (°C)/−100 to 1,500 (°F)
−200 to 400 (°C)/−300 to 700 (°F)
−199.9 to 400.0 (°C)/−199.9 to 700.0 (°F)
−200 to 1,300 (°C)/−300 to 2,300 (°F)
0 to 1,700 (°C)/0 to 3,000 (°F)
0 to 1,700 (°C)/0 to 3,000 (°F)
100 to 1,800 (°C)/300 to 3,200 (°F)
0 to 90 (°C)/0 to 190 (°F)
0 to 120 (°C)/0 to 240 (°F)
0 to 165 (°C)/0 to 320 (°F)
0 to 260 (°C)/0 to 500 (°F)
Either of the following ranges, by scaling:
−1,999 to 9,999
−199.9 to 999.9
0 to 2,300 (°C)/0 to 3,200 (°F)
0 to 1,300 (°C)/0 to 2,300 (°F)
Input temperature setting range
Either of the following ranges, by scaling:
−1,999 to 9,999
−199.9 to 999.9
−19.99 to 99.99
−1.999 to 9.999
Section 3-2