How to Use the Multi-SP Function

Using Event Inputs
Using Key Operations
76
Two set points are set externally by using the Number of Multi-SP Uses
parameter.
• Switching is possible between two set points (0 and 1) by setting the
Number of Multi-SP Uses parameter to 1. The default setting is 1 and
does not need to be changed to switch between two set points. Set points
0 and 1 are specified by the status of event input 1.
E5CN
11
EV1
12
+
EV2
13
+
E53-CN@B@N2 in the
E5CN-@M@-500 (for E5CN)
E5GN
7
8
EV1
+
EV2
9
+
The multi-SP function allows you to set up to four set points (SP 0 to 3) in the
adjustment level. The set point can be switched by operating the keys on the
front panel or by using external input signals (event inputs).
Two Event Inputs: Event Inputs 1 and 2
The following tables show the relationship between the ON/OFF combinations
of event inputs 1 and 2 and the selected set points.
Number of Multi-SP Uses = 1
Event input 1
OFF
ON
Number of Multi-SP Uses = 2
Event input 1
OFF
ON
OFF
ON
You can select any of the set points 0 to 3 by changing the set value of the
Multi-SP Uses parameter. The Multi-SP Uses parameter display conditions
are as follows:
• If the Controller does not support event inputs, the Multi-SP Uses param-
eter must be set to ON.
• If the Controller supports event inputs, the Number of Multi-SP Uses
parameter must be set to 0 and the Multi-SP Uses parameter must be set
to ON.
E5AN/EN
EV1
11
EV1
EV2
12
EV2
13
E53-AKB in the E5AN/EN-@M@-500-N
(for E5AN/EN)
EV1
EV2
Selected set point
Set point 0
Set point 1
Event input 2
OFF
OFF
ON
ON
Section 4-5
+
EV1
+
EV2
Selected set point
Set point 0
Set point 1
Set point 2
Set point 3