Wiring And Assembly Of Communications Connector And Mil Connector For Connector Terminals - Omron C200HW-SRM21-V1 - 08-2007 Operation Manual

Compobus/s system
Hide thumbs Also See for C200HW-SRM21-V1 - 08-2007:
Table of Contents

Advertisement

Connector Terminals
5-2-6
Wiring and Assembly of Communications Connector and MIL
Connector for Connector Terminals
Wiring
!Caution Be sure to turn OFF the Slave power supply and communications power sup-
1,2,3...
256
2. For details on wiring dimensions, refer to 5-2-3 SRT2-ID32ML (-1) Connec-
tor Terminals with 32 Transistor Inputs.
Connect the communications cable to the Connector Terminal using the rect-
angular communications connector provided with the Unit. The Connector
Terminals with MIL connectors are used to connect the external I/O. The wir-
ing and assembly methods of square communications connectors and MIL
connectors are described here.
The Connector Terminals with sensor connectors are used to connect the
external I/O cable connector. The cable connector wiring and assembly meth-
ods are the same as for Sensor Terminals, so refer to 3-4-3 Cable Connector
Wiring and Assembly for details.
A CompoBus/S cable must be connected to a Connector Terminal after the
communications data (BD H, BD L), communications power supply (BS+,
BS–), and I/O power supply (G, V) lines are connected to the communications
connector (i.e., the connector on the cable end). I/O power is not supplied to
32-point Connector Terminals.
ply before connecting communications data, communications power supply,
or I/O power supply lines, and before attaching or detaching connectors. For
the connector, use the communications connector provided with the Connec-
tor Terminal.
Use the following procedure to connect the communications data, communi-
cations power supply, and I/O power supply lines to the connector.
1. Remove sufficient insulation from the signal wires for a crimp terminal, and
twist the exposed wire strands together tightly.
If using VCTF cable, cover the severed end of the insulation with vinyl tape
or heat-shrinking tube.
2. After attaching a crimp terminal to the exposed signal wires, cover with vi-
nyl tape or heat-shrinking tube.
OMRON recommends the following products manufactured by Weidmuller
Co., Ltd. for use as crimp terminals.
Sleeve (product no. 046290)
Crimp terminal Cable
Insert cable then crimp
The following special tool is available:
Crimper PZ1.5 (product number 900599) manufactured by Weidmuller
Co., Ltd.
Apply vinyl tape or heat-
shrinking tube
For inserting 2 wires (product no. 901851)
Crimp terminal
Cable
Section 5-2