Ng System Data; Lp System Data; High Elevation; Gas Line Installation - Regency City CST50E Owners & Installation Manual

Direct vent
Table of Contents

Advertisement

installation - general

NG System Data

Max. Supply
14"WC (3.45 Kpa)
Pressure
Min. Supply
5" WC (1.25 kpa)
Pressure
Manifold Pressure
3.8" WC (0.87 kpa)
Orifice Size
#36 DMS
Maximum Input
35,000 Btu/h
(10.25 kW)
Minimum Input
19,000 Btu/h
(5.56 kW)

LP System Data

Max. Supply Pressure
14"WC (3.45 Kpa)
Min. Supply Pressure
11" WC (2.73 kpa)
Manifold Pressure
10.5" WC (2.49 kpa)
Orifice Size
#52 DMS
Maximum Input
33,000 Btu/h
(9.66 kW)
Minimum Input
17,000 Btu/h
(4.98 KW)

High Elevation

This unit is approved for altitude 0 to 4500 ft.
(CSA 2.17).

Gas Line Installation

Since some municipalities have additional local
codes, it is always best to consult with your local
authorities and the CSA B149.1 installation code.
For USA installations, follow local codes and/or
the current National Fuel Gas Code, ANSI Z223.1.
Use approved fittings with copper or flex connec-
tors. Always provide a union so that gas lines can
be easily disconnected for servicing. Flare nuts
for copper lines and flex connectors usually meet
this requirement.
Always check for gas leaks with a soap and
water solution or gas leak detector. Do not
use open flame for leak testing.
A shutoff / dante valve should be supplied in
or near the unit (or as per local codes) for
ease of servicing this appliance.
When an appliance is installed at elevations above
the maximum elevation option provided, the input
rate shall be reduced or air shutter opened further.
For altitudes above 4500' the input rate shall be
reduced at the rate of 4% for each additional 1000
ft (300 m). The input rate shall be reduced from
the rate indicated for the highest altitude option
provided.
This is to accurately adjust the input ratings of
appliances certified for high altitude to ensure proper
performance. The rated output of gas-burning
appliances decreases with higher altitudes due to
the reduction in atmospheric pressure.
48
| City Series CST50E
At higher elevations,and as an alternative, air
shutter settings may have to be opened more to
compensate for the lack of air.

Pilot Adjustment

Periodically check the pilot flames. Correct flame
pattern has two strong blue flames: 1 flowing around
the flame sensor and 1 flowing across the burner
(it does not have to touch the burner).
• If you have an incorrect flame pattern, contact
your Regency® dealer for further instructions.
Incorrect flame pattern will have small, probably
yellow flames, not coming into proper contact with
the rear burner or flame sensor.

Gas Pipe Pressure Testing

During pressure testing of the gas supply piping
system at pressures equal to or less than 1/2
psig. (3.45 kPa), close the appliance's manual
shut-off valve to isolated it from the gas supply.
Disconnect the piping from the valve at pressures
over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control and should be checked
at the pressure test point.
To properly check gas pressure, both inlet and
manifold pressures should be checked using
the valve pressure ports on the valve.
1
Make sure the unit is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide flat
screwdriver.
3. Attach manometer to "IN" and/or "OUT" pres-
sure tap(s) using a 5/16" ID hose.
4. Turn the unit on with the remote or wall switch.
5. The pressure check should be carried out with
the unit burning and the setting within the limits
specified on the safety label.
6. When finished reading the manometer, turn off
the unit, disconnect the hose, and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Screw should be snug, but do not over
tighten.

885 S.I.T. Valve Description

1) 6 Stage flame adjustment
2) Pilot adjustment
3) Inlet Pressure Tap
4) Outlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
4
3
2
1
5
6
7