Typical Installations - Flush TV Install

The clearances listed below are minimum requirements for either side of this see-through fireplace, unless otherwise noted.
A
E
D
B
C
B
A
Max. 2" (51 mm) to top of enclosure
B
Min. 1-1/2" (38 mm)
Chase vent min. open area:
175 sq. in. Bench Install
120 sq. in. Flush Install
C
Max. 5-1/2" (140 mm) (2 x 6 stud) See E for corresponding
min. height requirements.
D
Screws must not penetrate unit more than 1/2" (25 mm).
Adhere to "No Screw" zones painted on unit; glue is an ac-
ceptable alternative.
E
Min. 16-1/2" (419 mm) with 2 x 4 - dimension C
Min. 23-3/8" (594 mm) with 2 x 6 diemnsion C
F
Maximum 5-1/4" (133 mm)
G
Bottom of fireplace opening - combustible hearth shown.
F
A recess may be used on both sides if the clearance requirements
shown above are adhered to.
G
installation - general