Venting Arrangements For Vertical Terminations - Regency City CST50E Owners & Installation Manual

Direct vent
Table of Contents

Advertisement

installation-power vent
CV72EPV/CB72EPV/CB40EPV/CC40EPV/CV40EPV/CV60EPV
Inline Power Vent Vertical or Hortizontal Installation Instructions
Venting Arrangement for Vertical Terminations
Inline Power Vent Rigid/Flex
Venting Arrangement for Vertical Terminations-Inline Power Vent
Vertical venting with straight vertical venting and/or with a max. of six (6) 90
In line Power Vent Kit # 666-945
RIGID PIPE: MUST USE RIGID PIPE ADAPTOR 770-994 AND 946-606 PIPE REDUCER TO 4" X 6 5/8" (102 mm x 168 mm).
FLEX VENT: MUST USE REDUCER 946-758 TO 4" X 6 5/8" (102 mm x 168 mm).
Vertical venting with straight vertical venting and or with a max. of six (6) 90
• Rigid pipe is approved for up to 72 feet (22 m).
Rigid pipe is approved for up to 72 feet (22 m).
• Rigid pipe is approved for up to 72 feet (22 m).
Rigid pipe is approved for up to 72 feet (22 m).
• • Flex pipe is approved
Flex pipe is approved for up to 40 feet (12.2 m) using one 20 foot (6.1m) 20 foot Vertical Flex
• • Flex pipe is approved
Flex pipe is approved for up to 40 feet (12.2 m) using
kit (part # 946-755) & one 20 foot (6.1 m) extension flex kit (part # 946-756).
kit (part # 946-755) & one 20 foot (6.1 m) extension flex kit (part # 946-756).
two 20 foot (6.1 m) flex kits (part # 946-756).
two 20 foot (6.1 m) flex kits (part # 946-756).
Two 45
o
elbows equal to one 90
Vent must be supported at offsets.
Minimum distance between elbows is 1 ft. (0.3 m).
Maintain clearances to combustibles as listed in the
"Clearances" section.
Horizontal vent must be supported every 3 feet (0.91 m).
Firestops are required at each floor level and whenever
passing through a wall.
Restrictor set on 0 (fully open) regardless of vent run.
Inline power vent location restrictions:
Minimum 4 ft (1.2 m) from the unit.
Minimum 1 ft (0.3 m) prior to an elbow.
Minimum 1 ft (0.3 m) following an elbow.
Minimum 2 ft (0.6 m) prior to a termination cap.
Minimum 2 ft. from inline PV to termination cap.
Minimum 4' from top of unit to inline PV.
Max. of 72' (22 m), using up to six 90
(Example shows two 90
No negative runs.
• The inline power vent must be installed within the confines
The inline power vent must be installed within the confines
of the home/structure.
of the home/structure.
72
| City Series CST50E
920-210b
for up to 40 feet (12.2 m) using one 20 foot (6.1m) 20 foot Vertical Flex
for up to 40 feet (12.2 m) using
o
elbow.
0
elbows
elbows).
0
Min. 4' (1.22 m) from top of unit
Elbows (1 - 90
o
o
Max. of 72' (21.95 m), using up
(Note: two 90 elbows shown.)
to inline PV
2
2 - 45
)
o =
o
Elbows (1 - 90
2 - 45
o =
o
Min. 2' (0.61 m) from inline
PV to termination cap
Min. 4' (1.22 m) from
top of unit to inline PV
to six 90 elbows
0
0
3RD ANGLE
PROJECTION
DO NOT SCALE
DRAWING
UNITS IN INCHES
Min. 2' (0,61 m) from inline PV
to termination cap
)
TOLERANCES UNLESS
FIREPLAC
OTHERWISE STATED
INTER
DIMENSIONS
0.000 = 0.01 CRITICAL
1:24
SCALE:
0.000 = SPECIFIED TOLERANCE
0.000 = 0.031
MEDRA
DWN:
0.000 REF = REFERENCE ONLY
ANGULAR = 1
E.C.N.:
THIS DRAWING IS THE PROPERTY OF FPI LTD., IT MAY NOT BE COPIED IN W
09.22.20