If enabled, once the temperature reaches the Tunnel Set Point, Trio turns on the tunnel
fans and opens the tunnel doors. As in Basic Ventilation, you define the fans to be used in
each level. However, there is no curve between levels.
Even if Extra Ventilation is enabled, Trio will go straight to tunnel mode if the
temperature is above the Tunnel Set Point (skipping over Extra Ventilation).
You can set a differential for each level to ensure that ventilation increases only
when required.
In this example, tunnel fans are at level T6.
Refer to Tunnel Ventilation, page 56 for more details.