6.1.1 Setting the 5026 minimum ventilation (Stage 1)

1. Go to Cycle On.
2. Select Cycle.
3. Set the required parameters:
Cycle: Total cycle time
Min On: The minimum amount of time that the fans run
Change Step (%): The increase/decrease of fan time. For example, when the change is set to
10% and the fan is on for 50 seconds, it increases to 55 seconds.
Change Delay: The time, in seconds, before any change in cycle time occurs.
NOTE Even though Change Step and Change delay are set here, they only take effect during Stage 2.
4. Go to Stage 1.
5. Set the following parameters):
Temp On: Set the differential above the target temperature at which the fans begin (Band in
Figure 15)
Temp Off: Set the differential above the target temperature at which the fans end (Diff in Figure
15)
MV. Off: Set the differential below the target temperature at which MV ceases to operate

6.1.2 Setting 5026 Stage 2 and higher

1. Go to Stage 2.
NOTE If Stages 6 - 8 are set to Misting/Heating, set Stages 2 - 5 only.
2. Set the required parameters:
Temp On: Set the differential above the target temperature at which the fans begin
Temp Off: Set the differential above the target temperature at which the fans end
3. Repeat for each stage.

6.1.3 How does 5026 cooling work?

Ventilation time in the 5026 runs in three modes:
MV ramping timer: Fans run in an on/off cycle, where the cycle time changes as the
temperature changes.
Calculated on/off time: Fans continue running in a cycle, but change in cycle time only
happens after a user-defined delay. Since temperatures can fluctuate constantly, the delay
ensures stable fan speeds.
Continual operation: Fans remain on until the temperature drops
Figure 15 illustrates 5026 ventilation.